1. Without no-load voltage when started:
■Magnet field loss
■Check AVR reference signal connection
■Diode fault
■AVR fault
■Exciter field winding wiring open circuit(check the winding)
■Main rotor winding wiring open
2. Voltage too low
■ Check AVR wiring (AVR might have failed)
■ Field winding wiring short circuit
■Rotating diode damaged
■Main rotor winding wiring open
■Increase the rev(do not adjust the AVR voltage-potentiometer)
3. Voltage too high
■AVR failure
4. Voltage Oscillation
■ Check the rev: possibility of nonperiodical oscillation
■ Loose connection
■ AVR failure
■Engine rev is too low at loads or LAN configuration too high
5.The voltage is correct at no load while too low at load.
■ Rotating diode failure
■ Main rotor short circuit, check resistance
■ Exciter armature failure, check resistance
6. Voltage disappears during operation
■ Exciter field winding wiring open circuit
■ Exciter rotor failure
■ AVR failure
■ Main rotor open circuit or short